Telecommunication Infrastructure Standards prepared by IT Network Operations, revision 1.17, revision date March 2012. Establishes one campus’s labeling appendix: copper patch cords labeled with the switch and port number on the patch panel end and the patch panel and port number on the switch end; outside plant fiber labeled at each end with the far-end building name and number, mode and strand count, placed between 12 and 36 inches from a conduit and at 200-foot intervals along its run; riser fiber labeled on both ends with the far-end room number, strand count and mode. The document describes itself as a minimum standard and a starting point for collaboration, and names TIA/EIA-568-B and TIA/EIA-606-A, both superseded editions, so it is cited as a dated worked instance rather than as current requirements. Checked September 16, 2026.
The linked guide explains how this source informs its topic. Check the document’s scope and the edition adopted by your project before applying it. A publisher overview or product guide does not reproduce the full requirements of a standard.
Read the library’s edition and applicability notes.
What this source establishes
Cited for what one owner specified in 2012, including a reciprocal patch cord rule stated in a single sentence. No compliance outcome is inferred, and its cited standard editions are superseded.